Installation Sheet
RDM-3EM and RDM-6EM Energy Management Modules
The RDM-3EM (FG606-81) and RDM-6EM (FG606-80) are 3 and 6
Mounting
points
channel switching energy management modules. They are designed for use
with the RDA series of enclosures in an AMX Lighting™ system.
For more detailed installation and operating instructions, refer to the Radia
Lighting Control System Instruction Manual, available on-line at
1
The RDM-3EM and RDM-6EM are designed with the most advanced
latching energy management relays to support heavy duty commercial
applications, building automation, and loadside management. Equipped
with on-board module microprocessors, both support relay control and
sequencing. Features include:
Relays
(1-3)
2
3
•
User selectable delays in sequencing mode to minimize inrush current
and stress on the electrical distribution system.
•
Selectable strapping facilitates multiple relays on one Radia control
channel for large area control.
•
•
•
•
Manual on/off override on each relay independent of control system.
Relays retain their state during power and control system outages.
Visual Status Indicators on each relay.
Latching relays do not consume any control current, except when they
change state, eliminating the need for additional Radia power supplies.
Mounting
points
Control
Port
Sequencing
Delay Jumpers
(JP1 and JP2)
Strapping
Jumpers
(JP3 - JP4)
1
2
Relays
(1-6)
3
Mounting points
4
5
FIG. 2 RDM-3EM
RDM-3EM and RDM-6EM UL and C-Ul Ratings
•
General purpose: 120, 240, 277, and 347* VAC, 20 A
•
•
UL/CUL916 Energy Management Systems.
UL/CUL508 Industrial Control Systems.
6
Suggested Switched Loads
•
•
•
•
•
Incandescent
Fluorescent
Transformer
Low voltage
General purpose
Control
Port
Strapping
Jumpers
(JP3 - JP7)
Sequencing
Delay Jumpers
(JP1 and JP2)
Caution: Pre-Installation Notes
•
•
•
•
•
•
•
•
•
All Class 1 wiring must be connected to proper terminals.
All control wiring must be connected to proper terminals.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times.
Test loads for shorts before connecting.
Use low voltage wires with a 300 volt rating or greater.
Use field installed copper conductors.
All electrical ratings are for continuous duty.
For indoor use only.
Mounting points
FIG. 1 RDM-6EM
Specifications
•
•
•
•
•
•
•
Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
Non-phase dependant
Use wires rated at 75°C (167°F)
Torque terminals to 4.4 in lbs.
Wire size: 26 AWG to 10 AWG
Wire stripping length: 0.28" (7 mm)
Weight: 15 oz. (RDM-3EM) and 1.5 lbs. (RDM-6EM)
Included Accessories
•
•
4 mounting screws
Control wiring harness
*Agency approval pending
|